On Typical Flaws of the Transformer Models for Inrush Current Evaluation

Authors

Abstract

For many decades, the main, if not the only, equivalent circuit of a single-phase transformer was its T-model. To avoid ambiguity and take into account the topology of the core and windings, we will use the terms inner and outer windings, instead of the primary and secondary windings. So, inductances LS1 and LS2 are the so-called "leakage inductances" of the inner and outer windings, respectively, r1 and r2 are their resistances. In order to reproduce hysteretic (quasi-static) properties of the core material and to account for the dynamic core losses and saturation, the magnetizing branch is represented by an ATP-inductor DHM, which implements, starting with 2019 version, a Dynamic Hysteresis Model (DHM).

We have attracted attention to typical mistakes made in modeling transformer inrush currents. It is explained that the main mistake is the use of the convenient T-model and their three-phase derivatives. Their disadvantages are rooted in using separate leakage models of primary and secondary circuits, as well as in inability to reproduce different magnetization levels of the legs and yoke. We show the benefits of the π-model, but at the same time, caution against its oversimplification. Although we use an advanced hysteresis model to describe processes in the legs and yokes, it is shown that accounting hysteresis and core losses is completely optional in modeling inrush currents. These model properties have no visible impact neither on the current peaks nor their decay in time.

Downloads

Download data is not yet available.

References

H. Kr. Høidalen, L. Prikler, F. Peñaloza, ATPDraw, version 7.0 for Windows, User's Manual, 2019.

S. E. Zirka, Y. I. Moroz, N. Chiesa, R. G. Harrison, and H. Kr. Hoidalen, "Implementation of inverse hysteresis model into EMTP – Part II: Dynamic model," IEEE Trans. Power Del., vol. 30, no. 5, pp. 2233-3241, Oct. 2015. doi: 10.1109/TPWRD.2015.2416199.

A. Boyajian, Impedance characteristics of transformers. Ch. IV in Transformer Engineering L.F. Blume, G. Camilli, A. Boyajian, V.M. Montsinger, N.Y. John Wiley & Sons, 1938.

H. Altun, S. Sünter,·Ö. Aydoğmuş, "Modeling and analysis of a single-phase core-type transformer under inrush current and nonline-ar load conditions," Electrical Engineering. doi: 10.1007/s00202-021-01283-9.

A. Tokić, I. Uglešić, and G. Štumberger, "Simulations of trans-former inrush current by using BDF-based numerical methods," Hindawi Publishing Corp., Math. Problems in Eng., vol. 2013, Arti-cle ID 215647. http://dx.doi.org/10.1155/2013/215647.

J. Pedra, L. Sainz, F. Córcoles, R. Lopez, and M. Salichs, "PSPICE computer model of a nonlinear three-phase three-legged transformer," IEEE Trans. Power Del., vol. 19, no. 1, Jan. 2004. pp. 200-207. doi: 10.1109/TPWRD.2003.820224.

A. D. Theocharis, J. Milias-Argitis, and T. Zacharias, "Three-phase transformer model including magnetic hysteresis and eddy currents effects," IEEE Trans. Power Del., vol. 24, no. 3, pp. 1284–1294, Jul. 2009. doi: 10.1109/TPWRD.2009.2022671.

P. S. Moses, M. A. S. Masoum, and H. A. Toliyat, "Dynamic modeling of three-phase asymmetric power transformers with mag-netic hysteresis: No-load and inrush conditions," IEEE Trans. Energy Convers., vol. 25, no. 4, pp. 1040–1047, Dec. 2010. doi: 10.1109/TEC.2010.2065231.

C. M. Arturi, "Transient simulation of a three-phase five-limb step-up transformer following an out-of-phase synchronization," IEEE Trans. Power Del., vol. 6, no. 1, pp. 196–207, Jan. 1991. doi: 10.1109/61.103738.

N. Chiesa, B. A. Mork, H. K. Høidalen, "Transformer model for inrush current calculations: Simulations, measurements and sensi-tivity analysis," IEEE Trans. Power Del., vol. 25, no. 4, 2010, pp. 2599–2608. doi: 10.1109/TPWRD.2010.2045518.

S. V. Kulkarni and S. A. Khaparde, Transformer Engineering: Design and Practice. New York: Marcel Dekker, 2004.

S. E. Zirka, Y. I. Moroz, C. M. Arturi, N. Chiesa, and H. K. Høidalen, “Topology-correct reversible transformer model,” IEEE Trans. Power Del., vol. 27, no. 4, pp. 2037–2045, Oct. 2012. doi: 10.1109/TPWRD.2012.2205275.

S. Jazebi, F. de Leon, N. Wu. "Enhanced analytical method for the calculation of the maximum inrush currents of single-phase power transformers," IEEE Trans. Power Del., vol. 30, no. 6, pp. 2590–2599, Dec. 2015. doi: 10.1109/TPWRD.2015.2443560.

E. C. Cherry, "The duality between interlinked electric and magnetic circuits and the formation of transformer equivalent cir-cuits," Proc. Phys. Soc. B 62. pp. 101–111, 1949. doi: 10.1088/0370-1301/62/2/303.

S. Jazebi, S. E. Zirka, M. Lambert, A. Rezaei-Zare, et al., "Duality derived transformer models for low-frequency electromag-netic transients—Part I: Topological models," IEEE Trans. Power Del., vol. 31, no. 5, pp. 2410-2419, 2016. doi: 10.1109/TPWRD.2016.2517327.

F. de León, P. Gómez, J. A. Martinez-Velasco, and M. Rioual, “Transformers,” Chapter 4 in Power System Transients. Parameter Determination, J. A. Martinez-Velasco (ed.), CRC Press, 2009.

M. Kh. Zikherman, "Magnetization characteristics of large transformers," Elektrichestvo, no. 3, pp. 79-82, 1972. [in Russian].

H.W. Dommel, Electromagnetic transients program reference manual (EMTP Theory Book); Bonneville Power Administration, Portland, OR, USA, 1986.

S. Calabro, F. Coppadoro and S. Crepaz, "The measurement of the magnetization characteristics of large power transformers and reactors through DC excitation", IEEE Trans. Power Del., vol. 1, no. 4, pp. 224-232, Oct. 1986. doi: 10.1109/TPWRD.1986.4308052.

S. Jazebi, F. de León, A. Farazmand, and D. Deswal, "Dual reversible transformer model for the calculation of low-frequency transients," IEEE Trans. Power Del., vol. 28, no. 4, pp. 2509-2517, Oct. 2013. doi: 10.1109/TPWRD.2013.2268857.

W. Sima, B. Zou, M. Yang, F. de León, "New method to measure deep-saturated magnetizing inductances for dual reversible models of single-phase two-winding transformers," IEEE Trans. Power Del., vol. 36, no. 1, pp. 488-491, Feb. 2021. doi: 10.1109/TEC.2020.3023596.

H. Edelmann, "Descriptive determination of transformer equivalent circuits," Archiv für elektrische Übertragung, vol. 13, no. 6, pp. 253-261, 1959. [in German].

S. E. Zirka, Y. I. Moroz, C. M. Arturi, "Accounting for the in-fluence of the tank walls in the zero-sequence topological model of a three-phase, three-limb transformer," IEEE Trans Power Del., vol. 29, no. 5, pp. 2172–2179, Oct. 2014. doi: 10.1109/TPWRD.2014.2307117.

J. Zhao, S. E. Zirka, Y. I. Moroz, C. M. Arturi, "Structure and properties of the hybrid and topological transformer models," Int. J. Electr. Power & Energy Systems, vol. 118, 2020, 105785. doi: 10.1016/j.ijepes.2019.105785.

S. E. Zirka, Y. I. Moroz, A. V. Zhuykov, D. A. Matveev, et al., "Eliminating VT uncertainties in modeling ferroresonance phenome-na caused by single phase-to-ground faults in isolated neutral net-work," Int. J. Electr. Power & Energy Systems, 2021, vol. 133. Paper 107275. doi.org/10.1016/j.ijepes.2021.107275.

S. E. Zirka, Y. I. Moroz, J. Elovaara, M. Lahtinen, et al., "Simplified models of three-phase, five-limb transformer for studying GIC effects," Int. J. Electr. Power & Energy Systems, vol. 103, pp. 168-175, 2018. https://doi.org/10.1016/j.ijepes.2018.05.035.

Downloads

Published

2023-06-06

Issue

Section

Electronics and telecommunications

How to Cite

Zirka, S., & Moroz, Y. (2023). On Typical Flaws of the Transformer Models for Inrush Current Evaluation. Challenges and Issues of Modern Science, 1, 303-313. https://cims.fti.dp.ua/j/article/view/59

Share