Towards a comprehensive transient model of a large five-legged transformer under no-load conditions

Authors

Keywords:

transformer, dynamic modeling, no-load losses, supply voltage

Abstract

Large power transformers are related to the most responsible and expensive elements of electrical networks. Long-term operation of transformers without shutdowns requires taking into account energy losses in these devices and places high demands for the reliability of their modeling. The aim of this paper is to improve the dynamic model of a five-legged three-phase transformer used to reduce the overall height of the apparatus. The model under consideration develops the models and methods described earlier. The proposed improvements consist in a more detailed reproduction of the transformer operation under the no-load conditions at rated and increased supply voltage. The accuracy of the model is achieved by taking into account the hysteresis properties of the core, equivalent phase capacitances, and nonmagnetic gaps between the legs and yokes. The model's capabilities are illustrated by simulating a large five-legged transformer.
The object of study of this paper is the modeling of a 786 MVA step-up generator transformer and winding connection Yd11. The inner low voltage (LV) winding is connected in delta (d) with the liner voltage of 28 kV, whereas the liner voltage of the wye-connected (HV) outer winding (Y) is 525 kV. The rest of the transformer parameters are given in the literature.
The intermediate objective of the study is to model the transformer no-load losses in a wide range of LV. The second and main stage of the work is to reproduce the current waveforms in the three-phase line feeding the LV winding (the model has to cover LV voltages that reach 110% of the nominal value). It should be noted that the problem of calculating the current waveform was posed earlier, but no typical current curves were found in that work, and its authors limited themselves to modeling the transformer at rated voltage.

Downloads

Download data is not yet available.

References

Зирка, С. Е., Мороз, Ю. И., Мороз, Е. Ю., Тарчуткин А. Л. (2011). Моделирование переходных процессов в трехфазном трансформаторе с учетом топологии и гистерезисных свойств магнитопровода. Технічна електродинаміка, 5, 25–35.

Zirka, S. E., Moroz, Y. I., Elovaara, J., Lahtinen, M., Walling, R. A., Høidalen, H. Kr., Bonmann, D., Arturi, C. M., Chiesa, N. (2018). Simplified models of three-phase, five-limb transformer for studying GIC effects. Electrical Power and Energy Systems, 103, 168–175. https://doi.org/10.1016/j.ijepes.2018.05.035

Zirka, S. E., Albert, D., Moroz, Y. I., Renner, H. (2022). Further improvements in topological transformer model covering core saturation. IEEE Access, 10, 64018 – 64027. 10.1109/ACCESS.2022.3183279

Albert, D. (2022). Analysis of Power Transformers under DC/GIC Bias, PhD Thesis, Institute of Electrical Power Systems, Graz University of Technolоgy, Graz, Austria.

Carrander, C., Mousavi, S. A., & Engdahl, G. (2017). An application of the time-step topological model for three-phase transformer no-load current calculation considering hysteresis. Journal of Magnetism and Magnetic Materials, 423, 241–244. https://doi.org/10.1016/j.jmmm.2016.09.088

Zirka, S. E., Moroz, Y. I., Chiesa, N., Harrison, R. G. & Høidalen, H. K. (2015). Implementation of inverse hysteresis model into EMTP – Part II: Dynamic model, IEEE Transaction on Power Delivery, 5(30), 2233-3241. 10.1109/TPWRD.2015.2416199

Høidalen, H. K., Prikler, L., & Peñaloza, F. (2021). ATPDraw Version 7.3 for Windows. Users’ Manual, NTNU, Trondheim, Norway.

Nippon Steel catalog. (2019). https://www.nipponsteel.com/product/catalog_download/pdf/D004je.pdf

Elleuch, M. & Poloujadoff, M. (1998). New transformer model including joint air gaps and lamination anisotropy, IEEE Transaction on Magnetics, 5(34), 3701-3711. 10.1109/20.718532

Published

2024-06-14

Issue

Section

Engines, Energy and Thermotechnics

How to Cite

Zirka, S., & Albert, D. (2024). Towards a comprehensive transient model of a large five-legged transformer under no-load conditions. Challenges and Issues of Modern Science, 2, 65-71. https://cims.fti.dp.ua/j/article/view/125

Share